VS-8967 Portable DC Ground Fault Finder

▲ The system's ground voltage measurement function, the instrument can measure the system's positive ground voltage, negative ground voltage, and system voltage, and can achieve a voltage monitoring range of 0~300V.▲ System insulation resistance measurement function, the instrument can measure the system's positive-to-ground insulation resistance and negative-to-ground insulation resistance, and can achieve a measurement of 0~999KΩ.▲ AC string detection function, the instrument can judge the AC string fault in the DC system, and can measure the AC voltage value in the DC system. The AC voltage measurement range is 0~280V.

Tel:0086+400-996-1868

■ Features

▲ The system's ground voltage measurement function, the instrument can measure the system's positive ground voltage, negative ground voltage, and system voltage, and can achieve a voltage monitoring range of 0~300V.

▲ System insulation resistance measurement function, the instrument can measure the system's positive-to-ground insulation resistance and negative-to-ground insulation resistance, and can achieve a measurement of 0~999KΩ.

▲ AC string detection function, the instrument can judge the AC string fault in the DC system, and can measure the AC voltage value in the DC system. The AC voltage measurement range is 0~280V.

▲ Branch circuit insulation resistance measurement function, the instrument measures the positive and negative insulation resistance of each branch circuit to ground.

▲ The branch circuit ground fault point location function, the instrument can realize the ground fault branch circuit ground fault point location function.

▲ With ammeter function, the device can be used as a high-precision ammeter, and the current measurement resolution can reach 0.01mA.

▲ It has the function of non-signal grounding search. The device can locate the ground fault point without injecting any signal into the system.

▲ Direction display function. For branch circuits with grounding indications tested, the instrument will have direction indication arrows to remind users of the relative direction between the grounding point and the grounding point being searched, which improves the search efficiency.

▲ Insulation index analysis function. When using the grounding function to detect, after detecting a branch, the detector will display the insulation index of the branch for the user's reference and analysis.

▲ Wave curve display function. When using the detector to detect the insulation condition of the branch under test, the display will display the current change of the branch under test in the form of a wave curve, which is convenient for users to find fault points quickly and accurately.

■ Analyzer technical parameters

▲ Applicable DC system voltage level: 48V, 110V, 220V or user specified voltage level

▲ Measuring range of system positive and negative voltage: 0~300V

▲ Measuring range of DC voltage to ground: 0~300V

▲ Measuring range of AC voltage to ground: 0~300V

▲ Alarm threshold for AC serial power failure: 5V

▲ Voltage measurement resolution: 0.1V

▲ Measuring range of system resistance to ground: 0~999.9KΩ

▲ Measurement resolution of ground resistance: 0.1KΩ

▲ Display mode: LCD

▲ Detection signal current size: 0~2mA adjustable

▲ Detection signal voltage amplitude: 0~50V adjustable

▲ Signal frequency: no signal mode and 0.16Hz optional

▲ Anti-DC system distributed capacitance interference: 1000uF

■ Detector technical parameters

▲ Detection range of branch insulation resistance in signal mode:

       The system voltage level is 220V: 0~600KΩ

       The system voltage level is 110V: 0~300KΩ

       The system voltage level is 48V: 0~60KΩ

       Insulation resistance measurement resolution: 0.1KΩ

▲ Detection range of branch insulation resistance in no signal mode:

       The system voltage level is 220V: 0~50KΩ

       The system voltage level is 110V: 0~25KΩ

       The system voltage level is 48V: 0~10KΩ

▲ Insulation resistance measurement resolution: 0.1KΩ

▲ Waveform display time: 12 seconds

▲ Current measurement range: ±100mA

▲ Current measurement resolution: 0.01mA

▲ Display mode: LCD

▲ Direction display mode: same direction or reverse mark

▲ Anti-DC system branch circuit distributed capacitance interference: 100uF

▲ Use distance between analyzer: no distance limit

▲ Jaw size: Ф30mm