■ Product Overview
Vspd-200/200a PARTIAL discharge tester can be used together with uHF sensors, TEV sensors, acoustic and electrical combination sensors, ultrasonic sensors and broadband current transformers (HFCT) online detection of partial discharge transformers, high voltage switchgear, GIS, cable connectors and other high voltage equipment. Easy to carry, fast measurement, strong anti-interference ability, easy to use on site.
Its configuration software with real-time waveform figure, large peak display, positioning, and other functions, the software can also be a detailed survey analysis phase waveform, window zoom in and out at will, also can undertake spectrum analysis of this data, analysis of the discharge waveform frequency content, more comparability between the discharge waveform, comprehensive statistical analysis of test data, Reduce the influence of non-stability factors on test results.
The instrument adopts automatic or manual record to save test data and transient discharge waveform, providing reference for later data analysis.
Vspd-200 has two measuring channels, and VSPD-200A has four measuring channels.
■ Technical parameters
Technical characteristics | According to | ||
The channel number | 2/4 electrical signal interface, 1 external synchronization interface | display | 6.5-inch TFT true color touch LCD screen |
Sampling rate | 200MSa/s | The resolution of the | 640×480 |
The sampling accuracy | 12bit | storage | |
Scale range | 100dB | Physical storage | 4GB |
Switch range | 0-9 共 10 档 | The hard disk | 32G solid state disk for storing test records and test data |
Frequency range | 1Hz-60MHz | Configuration list | |
Nonlinear error of this range | 5% | The host | Used for signal acquisition, waveform display, data processing, storage |
Detection sensitivity | ≥5pC (under laboratory conditions); ≥10pC (field condition) | Ultrasonic transducer | Ultrasonic transducer |
Atlas display mode | 2 d PPRS display, 3 D PRPD display, sine display Display, statistics, spectrum (AE) 5 display | Detection frequency band | 20 ~ 200kHz |
The sensitivity | ≤10 pC | ||
The power supply mode | Built-in lithium battery /AC 220V | gain | 40dB |
interface | Uhf sensor(UHF) | Used to measure uHF signals generated by partial discharge in GIS | |
RS232*1 | It is used to synchronize the transmission interface with the PC | Detection frequency | 300 ~ 1500MHz |
USB*2 | External mouse keyboard, as well as external mobile storage devices | HFCT(High-frequency current transformer) | Used to measure partial discharge signals in the grounding cable of the device |
The power supply mode | Battery power (16.8V lithium battery) + external power supply(220V AC) | Detection of band | 500kHz ~ 30MHz |
Electrical interface | 2/4 BNC ports for signal input | Detection sensitivity | 10pC |
E-Trig interface | External synchronization interface | TEV The sensor | Used for measuring partial discharge and positioning of high voltage equipment such as switch cabinet |
So * 1 | Used to connect to a network | Signal acquisition | capacitive |
Grounding button | External grounding | Detection frequency | 3 ~ 100MHz |
General instructions | Measuring range | 0 ~ 60dB | |
CPU | frequency 1.6GHz | Combined acoustoelectric detector | Used to measure partial discharge of cable connector |
system | WIN7 | Ultrasonic transducer | Used for measuring ultrasonic signal generated by partial discharge of cable joint |
Ambient temperature | -20℃~60℃ | Center frequency | 40kHz |
Storage Environment Temperature | -20℃~85℃ | The sensitivity | ≤10 pC |
Overall dimensions | 280mm×190mm×80 mm | Electric signal sensor | Used for measuring electromagnetic wave signal generated by partial discharge of cable joint |
The weight of the | 3.5kg | Detection frequency band | 20k ~ 1MHz |
The sensitivity | ≤10 pC |