■ functional features of high voltage circuit breaker analyzer
▲ time: inherent opening and closing time of 12 fractures, in-phase synchronization and phase to phase synchronization.
▲ reclosing: closing opening, opening closing, opening closing opening process time of each fracture: one opening time, one closing time, two closing time, golden short time and no current time value.
▲ bouncing: closing bouncing time, bouncing times, bouncing process and bouncing waveform of each fracture; Opening rebound amplitude of each fracture.
▲ speed: rigid opening and closing speed, speed, time stroke characteristic curve.
▲ stroke: total stroke, opening distance, overtravel, overshoot stroke, rebound amplitude.
▲ current: opening and closing current value and current waveform diagram of opening and closing coils.
▲ operating voltage: dc30 ~ 250V / 20A digital adjustable circuit breaker operating power supply is provided in the machine to automatically complete the low-voltage operating test of the circuit breaker and measure the operating voltage value of the circuit breaker.
■ technical parameters
▲ time:
● measuring range: 4000.0ms, resolution: 0.1ms
● error: ① 0.1ms ± 1 word within 100ms ② 0.1% ± 1 word above 100ms ③ synchronization
▲ speed:
● measuring range: 20.00m/s, resolution: 0.01m/s
● error: ① within 0-2m / s ± 0.1m/s ± 1 word ② above 100ms ± 0.2m/s ± 1 word
▲ stroke:
range | Resolution | error | |
Vacuum circuit breaker | 50.0mm | 0.1mm | 1%±1 word |
SF6 circuit breaker | 300.0mm | 1mm | |
Low oil circuit breaker | 1000.00mm |
▲ current: range 20.00a, resolution 0.01A, load change rate: ≤ 1%
▲ DC power supply: adjustment range: 15 ~ 260V
▲ graphic display: 0.1ms per channel
▲ output power supply: dc15 ~ 260V digital adjustable / 20A (instantaneous operation)
▲ overall dimension: 360mm × 280mm × 300mm
▲ weight: 9kg
Vs-5308b Siemens graphite contact switch test can accurately test graphite contact
Dynamic resistance waveform, time and synchronization of 3 or 6 fractures of head switch